Variable Frequency Drive RepairVariable Frequency Drive Repair

Timely variable frequency drive repair can be crucial to industrial manufacturing. Drive replacement can be expensive and prolonged lead times for OEM drive repair is also a very common problem. Ask an engineer the purpose of a variable frequency drive (VFD), and a common answer would be “to save energy.” While the motivation to increase energy efficiency could be financial (reduced energy costs) or ethical (reduce greenhouse gas emissions associated with power production), it is taken for granted that VFDs are an easy way to improve energy efficiency in a motor application.

With these noble intentions in mind, the engineer will specify a VFD for his client. Oftentimes, that isn’t the end of the story for the engineer.

The story sometimes ends badly with a dead motor or a building with power quality issues, an understandably angry client, and a lot of finger-pointing. These outcomes are often the result of a poor understanding of Variable Frequency Drive Repair and how motors work in conjunction with the loads they serve. Come to CMI for Variable Frequency Drive Repair if you live in Houston or the greater Houston Metro area.

The information and claims from manufacturers and vendors often serve to further confuse the issues. Following are a few basic guiding concepts to dispel some of this confusion surrounding the matching of VFDs and motors to fans and pumps typically encountered in commercial building applications.

Variable Frequency Drive Repair: Anatomy of an Induction Motor

Electric motors convert electrical energy into rotational mechanical energy. Motors may drive pumps, fans, compressors, or any other number of loads that may be found in a typical building. The concept seems simple, but a review of motor basics is necessary to understand how VFDs operate and also how they can destroy a motor.

Variable Frequency Drive Repair

The most common motor encountered in commercial building multi-horsepower applications is a 3-phase ac induction motor. The motor consists of two primary assemblies: a stationary stator and a rotating rotor. Alternating current flows through windings in the stator, creating a rotating magnetic field around the rotor.

The frequency of this rotating magnetic field is directly related to the frequency of the ac voltage source. This rotating magnetic field interacts with rotor, inducing current in the rotor and an associated tangential force, which ultimately causes the rotor to turn. In an induction motor, the speed of the rotor is always slower than that of the rotating field.

The torque of the motor is roughly proportional to the power of the motor and inversely proportional to the speed of rotation. This operational characteristic is important when considering if a variable torque load (centrifugal fan, pump, or compressor) or a constant torque load (positive displacement screw, scroll, or reciprocating compressor) will be connected to the motor.

The most common type of induction motor is the squirrel cage motor (also called short-circuit rotor type motor). The stator consists of doughnut-shaped sheets of steel called laminations. These laminations have slots punched in them and then are aligned and stacked together. Conductors are then wound through these slots to form coils. These coil conductors are electrically insulated from the laminations.

The characteristics of this insulation system are important later in our discussion. The cylindrical rotor fits in the void in the middle of the stator. Like the stator, the rotor is made from stacked steel laminations. These laminations are pressed onto a center shaft. Bars of aluminum or copper are inserted through slots at the outer edge of the lamination and are connected at the ends with shorting rings at either end to form a cage-like structure.

The rotor is supported with bearings at the ends of the shaft. There is no direct electrical connection between the rotor and the windings in the stator. The only point of contact is at the bearings, which will be important in a later section.

Induction motors are not 100 percent efficient. Motor energy loss is caused by several factors, including I2R power losses, magnetic core losses, friction losses, and stray load losses. These losses generally result in heat generation, which must be dissipated to preserve the motor winding insulation. For common totally enclosed fan-cooled motors (TEFC), this heat dissipation is accomplished using a fan coupled to the rotor shaft.

The speed of the motor will directly affect volume of cooling air produced by this fan. As such, the speed of the motor is an important consideration when variable speed motor operation is desired. As a rule of thumb, a 10 C increase in winding temperature will halve the life expectancy. Conversely, a 10 C decrease in winding temperature will double the life expectancy.

Standard insulation classes for squirrel cage induction motors a

  • B (80 C): general purpose
  • F (105 C): industrial use
  • H (125 C): special use, heavy duty

These ratings reflect internal temperature rise only. The maximum recommended temperature limit for any motor also factors in ambient temperature and an extra 10 C hot-spot temperature within the windings. Therefore, a motor with Class B insulation designed to operate in a 40 C ambient would have a maximum recommended operating temperature of 130 C. Motors using higher rated insulation systems may run hotter to take advantage of the improved insulation, but also would pack more power into a smaller package.

Via CSEMag

You can trust Community Motors Inc. for Variable Frequency Drive Repair as the premier provider of all your Electrical, Motor Rewind and Generator needs in the Texas communities of:

Houston, Beaumont, Spring, Pasadena, Huntsville, Humble, Conroe, Bryan, Galveston, College Station, Katy, Sugar Land, Lufkin, Baytown, Kingwood, Port Arthur, Pearland, Cypress, Magnolia, Richmond, Orange, Texas City, Tomball, Rosenberg, League City, Montgomery, Livingston, Bellaire, Bay City, Missouri City, Santa Fe, La Porte, Stafford, Alvin, Willis, Friendswood, Angleton, Freeport, Brenham, Cleveland, Huffman, Splendora, New Waverly, Caldwell, Shepherd, Liberty, Eagle Lake, Fulshear, Hitchcock, Bellville, San Felipe, Hockley, Starks, Barker, Vinton, Dayton, Sealy, Dickinson, Weimar, Crockett, Channelview, El Campo, Lake Jackson, Deer Park, Jasper, Alief, Cameron, Kemah, Brazoria, Wharton, Groves, North Houston, Hungerford, Needville, Crosby, Kountze, Porter, Simonton, Bacliff, Seabrook, Hempstead, Anahuac, Port Bolivar, Trinity, Kirbyville, Hankamer, Webster, Brookshire, New Caney, Columbus, La Marque, Navasota, Riverside, Waller, Fresno, Highlands, China. Be sure to check us out on Facebook.